Automation Industrielle | Module entrée-sortie distribués | FR-8C


Caractéristiques détaillées:
8-channel open collector output module
Functional Description The FR-8/16/32C has 8/16/32-channel open collector output. Not like traditional digital I/O board, the FR series I/O module has an FRnet interface. It can be used as a distributed remote I/O module or a MagicWire module. The user should select the correct setting when using these modules. The user can daisy chain several FRnet modules together. Via FRnet, the FRnet modules can work with PC, PAC, £gPAC and PLC easily. Further information about the networking of FR-8/6/32C, refer to our I-7188EF, I-8122, FRB-100/200.
Applications
Specifications
Features
8-channel open collector output module
Functional Description The FR-8/16/32C has 8/16/32-channel open collector output. Not like traditional digital I/O board, the FR series I/O module has an FRnet interface. It can be used as a distributed remote I/O module or a MagicWire module. The user should select the correct setting when using these modules. The user can daisy chain several FRnet modules together. Via FRnet, the FRnet modules can work with PC, PAC, £gPAC and PLC easily. Further information about the networking of FR-8/6/32C, refer to our I-7188EF, I-8122, FRB-100/200.
Applications
- Factory Automation
- Building automation
- Energy management
- Agriculture automation
Specifications
- Communication speed: 250K bps
- Communication distance: 400m max
- Number of channels: 8/16/32 ( FR-8/16/32C)
- Open-collector: each chanenl 30V@100mA
- Power Requirement: 10~30V
- Wire cable: CPEV 0.9S (2P Twisted-pair wire)
- Power consumption:
24V@25mA(max) ( FR-8C)
24V@75mA(max) ( FR-16C)
24V@140mA(max) ( FR-32C) - Operating temperature: -25¢XC ~ +75¢XC
- Operating humidity: 10% ~ 90% RH, non-condensing
- Storage temperature: -30¢XC ~ +85¢XC
- Storage humidity: 5% ~ 95% RH, non-condensing
- Dimensions:
103 mm x 86 mm ( FR-8C)
147 mm x 76 mm (FR-16C)
173 mm x 117 mm (FR-32C)
Features
- Built-in FRnet interface
- Real I/O synchronization
- Innovative token-stream technology
- Support Broadcasting
- Real Deterministic Control
- Fixed Scan time: 256 points @ 2.88 ms
- Each bank consists of 8 input channels and has its own ground reference
- ASIC design without CPU
- Memory-map I/O
- No protocol and no software overhead
- Easy Programming and OS-independent
- Din-rail mounting
- Two-Wire Cabling
- Jumper setting
- Interface circuit
Spécifications:
Communication speed
250K bps
Communication distance
400m max
Number of channels
8/16/32 ( FR-8/16/32C)
Open-collector
each chanenl 30V@100mA
Power Requirement
10~30V
Wire cable
CPEV 0.9S (2P Twisted-pair wire)
Operating temperature
-25¢XC ~ +75¢XC